Voltage Jumper selectable
100-130 Vac 1 phase or
190-264 Vac 1 phase
Frequency 50-60 Hz nominal
POWER INPUT
voltage 100-264 V ac 1 phase
Frequency 50-60 Hz nominal
OUTPUT
Voltage 82 V d.c. @ 200 V a.c.
Current continuous 4A (see note 1).
transient 7.5A for 10 secs.
Resistance 15 ohms min (10 ohms min when input volts is less than 175 ac)
REGULATION
+/- 1.0% (see note 2)
THERMAL DRIFT
0.03% per deg. C change in AVR ambient (see note 3)
TYPICAL SYSTEM RESPONSE
AVR response 20 ms
Filed current to 90% 80 ms
Machine Volts to 97% 300 ms
EXTERNAL VOLTAGE ADJUSTMENT
+/-10% with 1 k ohm 1 watt trimmer (see note 4)
Increasing resistance lowers voltage.
UNDER FREQUENCY PROTECTION
Set point 94 -98% Hz (see note 5)
UNIT POWER DISSIPATION
12 watts maximum
BUILD UP VOLTAGE
4 Volts @ AVR terminals
ANALOGUE INPUT
Maximum input +/- 5 Vdc (see note 6)
Sensitivity 1V for 5% Generator Volts (adjustable)
Input resistance 1k ohm
QUADRATURE DROOP INPUT
10 ohms burden
Max. sensitivity: 0.07 A for 5% droop 0PF
Max. input: 0.33 A
OVER EXCITATION PROTECTION
Set point 65 V dc
Time delay 10-15 seconds (fixed)
ENVIRONMENTAL
Vibration 20-100 Hz 50mm/sec
100Hz – 2kHz 3.3g
Operating temperature -40 to +70C (note 7)
Relative Humidity 0-70C 95% (note 8)
Storage temperature -55 to +80C